Is Link11 down?
Last checked just nowNo incidents right now.
Link11 is operational right now. Last checked just now; the most recent incident resolved 16h ago.
Real-time Link11 status, recent outages, and incident history: pulled directly from Link11's official status page at link11.statuspage.io every 5 minutes. Pingoru tracks 8 Link11 services and has captured 12 incidents in the last 90 days (97.22% uptime). Get email, Slack, Discord, or webhook alerts the moment Link11 reports a new incident, free for 3 monitors, no credit card.
Recent outages & incidents
Past 90 days- Infrastructure Protection
Timeline · 2 updates
- identified · Oct 30, 2026, 04:39 PM UTC
We are currently experiencing intermittent connectivity issues at our Ashburn site. Link11 is actively working with its transport providers to restore services as quickly as possible. We will provide further updates as soon as more information becomes available.
- resolved · Oct 30, 2026, 10:04 PM UTC
Cogent has restored data transport service on one of the affected lines, and the Ashburn site and associated services are now back to normal. This incident is now resolved; no further updates will follow.
Latest: Cogent has restored data transport service on one of the affected lines, and the Ashburn site and associated services are now back to normal. This incident is now resolved; no furt…
-
- Link11 WAAP
Timeline · 3 updates
- identified · Oct 30, 2026, 04:37 PM UTC
Dear valued Customer, We are currently experiencing an outage affecting the Link11 support mailboxes. During this time, emails sent to our support team may not be received or may be delayed. If you need assistance, please contact our 24/7 Support Hotline at +49 69 5800 4926-99. Our team is available and ready to help. If you have sent an email to support since 30 October 2026, 12:00 UTC, we recommend calling the hotline so we can make sure your request is handled. Our teams are actively working to restore the service, and we will keep you informed on our progress. We apologize for any inconvenience and thank you for your patience. Kind regards, — Link11 Customer Support Team
- monitoring · Oct 30, 2026, 04:51 PM UTC
Dear valued Customer, The outage affecting the Link11 support mailboxes has been resolved. Emails sent to our support team are being received again. We are continuing to monitor the service closely to make sure it stays stable. If you emailed support between 30 October 2026, 12:00 UTC and 30 October 2026, 16:45 UTC and have not had a reply, please send your request again or call our Support Hotline at +49 69 5800 4926-99 so we can make sure it is handled. We apologize for the inconvenience and thank you for your patience. Kind regards, — Link11 Customer Support Team
- resolved · Oct 30, 2026, 06:54 PM UTC
Dear Customer, After a period of monitoring, we can confirm that the Link11 support mailboxes are stable and working normally. This incident is now Resolved. You can reach our support team by email again as usual. If you still have an open request from the time of the outage that has not been answered, please email us or call our Support Hotline at +49 69 5800 4926-99. Thank you for your patience and understanding. Kind regards, — Link11 Customer Support Team
Latest: Dear Customer, After a period of monitoring, we can confirm that the Link11 support mailboxes are stable and working normally. This incident is now Resolved. You can reach our supp…
-
-
Timeline · 2 updates
- investigating · Oct 04, 2026, 07:51 PM UTC
We are currently investigating some intermittent issues with our phone lines. Some of the calls are not being properly forwarded. Please use the following International number as the main one for the time being in case you having issues using our other numbers +972 73 200 52 00 — Link11 Customer Support Team
- resolved · Oct 05, 2026, 02:00 PM UTC
This incident has been resolved.
Latest: This incident has been resolved.
-
- Web DDoS ProtectionLink11 WAAP
Timeline · 4 updates
- investigating · Sep 24, 2026, 08:55 PM UTC
We are currently investigating intermittent errors / degraded performance in SG. If you are experiencing impact beyond the above, please contact our support team through the usual channels. — Link11 Customer Support Team
- identified · Sep 24, 2026, 09:17 PM UTC
The issue has been identified and a fix is being implemented.
- monitoring · Sep 24, 2026, 09:27 PM UTC
A fix has been implemented and we are monitoring the results.
- resolved · Sep 24, 2026, 10:47 PM UTC
This incident has been resolved.
Latest: This incident has been resolved.
-
- Infrastructure ProtectionWeb DDoS ProtectionSecure CDNSecure DNSLink11 WAAP
Timeline · 14 updates
- investigating · Aug 15, 2026, 05:09 AM UTC
We are currently investigating a potential issue affecting Link11 WAAP and Infrastructures connections in FFM7 (FR5). Traffic is being rerouted to alternative locations where possible. Our engineering teams are actively investigating with high priority. Customer traffic protection remains our top focus, and we will share a further update as soon as we have more information. If you are experiencing impact beyond the above, please contact our support team through the usual channels. — Link11 Customer Support Team
- identified · Aug 15, 2026, 06:28 AM UTC
Datacenter outage occurring in FFM7 Equinix, due to a leaking chiller loop that is causing high temperatures. The customer traffic has been re-routed from affected systems.
- identified · Aug 15, 2026, 09:06 AM UTC
We are still waiting for on-site access to the datacenter (FFM7 Equinix) to address the leaking chiller loop causing high temperatures. Customer traffic remains rerouted away from the affected systems, and our engineering team continues to monitor the situation closely. We understand the impact this ongoing incident may have and appreciate your patience. We will share the next update as soon as we have confirmation of access or further developments. If you're experiencing impact beyond what's described here, please reach out to our support team through the usual channels.
- identified · Aug 15, 2026, 12:17 PM UTC
Aug 15, 2026 - 12:15 UTC: Update - Restoration work at the affected datacenter FFM7 (FR5 Equinix) is ongoing and is being carried out by the facility operator. On-site access to our equipment has not yet been possible; we are in continuous contact with the operator to obtain access as soon as conditions allow. Customer traffic remains rerouted away from the affected systems. As parts of our infrastructure at this location are still unavailable, full service verification is ongoing and some management and reporting functions may be temporarily limited. We will provide the next update as soon as we have confirmed access to the site or further relevant developments. If you are experiencing impact beyond what is described here, please contact our support team through the usual channels.
- identified · Aug 15, 2026, 02:53 PM UTC
Aug 15, 2026 - 14:53 UTC Update - Restoration work at the affected datacenter (FFM7 Equinix) is still ongoing. The facility operator has confirmed that leaks in the chilled water cooling system caused water ingress into parts of the facility, resulting in the loss of cooling and elevated temperatures that forced affected systems offline. The leaks have since been isolated and the operator is working on restoring the cooling infrastructure. However, access to the affected areas - including our equipment - remains restricted for safety reasons, and no on-site work has been possible yet. We remain in continuous contact with the operator and have recovery hardware and personnel on standby to begin restoration as soon as access is granted. Customer traffic remains rerouted away from the affected systems. Some management and reporting functions remain temporarily limited. We will provide the next update as soon as we have additional information, at the latest by 16:55 UTC (18:50 CEST). If you are experiencing impact beyond what is described here, please contact our support team through the usual channels.
- identified · Aug 15, 2026, 06:35 PM UTC
Update - Restoration work at the affected datacenter (FFM7 Equinix) is still ongoing. The facility operator has confirmed that leaks in the chilled water cooling system caused water ingress into parts of the facility, resulting in the loss of cooling and elevated temperatures that forced affected systems offline. The leaks have since been isolated and the operator has restored cooling for the majority of the datacenter. However, access to the affected areas - including our equipment - remains restricted for safety reasons, and no on-site work has been possible yet. We remain in continuous contact with the operator and have recovery hardware and personnel on standby to begin restoration as soon as access is granted. Customer traffic remains rerouted away from the affected systems. Some management and reporting functions remain temporarily limited. We will provide the next update as soon as we have additional information, at the latest by 19:00 UTC (21:00 CEST). If you are experiencing impact beyond what is described here, please contact our support team through the usual channels.
- identified · Aug 15, 2026, 09:41 PM UTC
Update - Restoration work at the affected datacenter (FFM7 Equinix) is still ongoing. The facility operator has confirmed that leaks in the chilled water cooling system caused water ingress into parts of the facility, resulting in the loss of cooling and elevated temperatures that forced affected systems offline. The leaks have since been isolated and the operator has restored cooling for the majority of the datacenter. However, access to the affected areas - including our equipment - remains restricted for safety reasons, and no on-site work has been possible yet. We remain in continuous contact with the operator and have recovery hardware and personnel on standby to begin restoration as soon as access is granted. Customer traffic remains rerouted away from the affected systems. Some management and reporting functions remain temporarily limited. We will provide the next update as soon as we have additional information, at the latest by 23:59 UTC. If you are experiencing impact beyond what is described here, please contact our support team through the usual channels.
- identified · Aug 16, 2026, 01:48 AM UTC
Update - Restoration work at the affected datacenter (FFM7 Equinix) is still ongoing. The facility operator has confirmed that leaks in the chilled water cooling system caused water ingress into parts of the facility, resulting in the loss of cooling and elevated temperatures that forced affected systems offline. The leaks have since been isolated and the operator has restored cooling for the majority of the datacenter. However, access to the affected areas - including our equipment - remains restricted for safety reasons, and no on-site work has been possible yet. We remain in continuous contact with the operator and have recovery hardware and personnel on standby to begin restoration as soon as access is granted. Customer traffic remains rerouted away from the affected systems. Some management and reporting functions remain temporarily limited. We will provide the next update as soon as we have additional information, at the latest by 03:59 UTC. If you are experiencing impact beyond what is described here, please contact our support team through the usual channels.
- identified · Aug 16, 2026, 04:42 AM UTC
Update - Restoration work at the affected datacenter (FFM7 Equinix) is still ongoing. The facility operator has confirmed that leaks in the chilled water cooling system caused water ingress into parts of the facility, resulting in the loss of cooling and elevated temperatures that forced affected systems offline. The leaks have since been isolated and the operator has restored cooling for the majority of the datacenter. However, access to the affected areas - including our equipment - remains restricted for safety reasons, and no on-site work has been possible yet. We remain in continuous contact with the operator and have recovery hardware and personnel on standby to begin restoration as soon as access is granted. Customer traffic remains rerouted away from the affected systems. Some management and reporting functions remain temporarily limited. We will provide the next update as soon as we have additional information, at the latest by 07:00 UTC. If you are experiencing impact beyond what is described here, please contact our support team through the usual channels.
- identified · Aug 16, 2026, 06:35 AM UTC
Aug 16, 2026 - 06:35 UTC We have now been granted access to the affected datacenter FFM7 (FRA5 Equinix). The facility operator has completed cooling restoration, and temperatures in the affected areas have returned to normal operating ranges. Our technicians are on their way to the site and will begin with a detailed assessment of our equipment, followed by a controlled, staged restoration of the affected systems. Replacement hardware has been prepared in advance and is available if required. Customer traffic remains rerouted away from the affected systems and stays protected throughout the restoration. Some management and reporting functions remain temporarily limited; restoring these is being worked on in parallel. As the restoration will be performed carefully in stages, we cannot yet provide a completion time. We will provide the next update once the on-site assessment is complete, at the latest by 10:00 UTC. If you are experiencing impact beyond what is described here, please contact our support team through the usual channels.
- identified · Aug 16, 2026, 07:40 AM UTC
Update - Aug 16, 2026 - 07:40 UTC Our technicians have arrived at the datacenter FFM7 (FRA5 Equinix) and have started the on-site assessment of our equipment. Once the assessment is complete, the controlled, staged restoration of the affected systems will begin. Customer traffic remains rerouted away from the affected systems. Some management and reporting functions remain temporarily limited. We will provide the next update once the assessment results are available, at the latest by 12:00 UTC (14:00 CEST). If you are experiencing impact beyond what is described here, please contact our support team through the usual channels.
- identified · Aug 16, 2026, 09:26 AM UTC
Update - Aug 16, 2026 - 09:25 UTC The on-site assessment has been completed and we have started to gracefully power the affected location (FFM7) back up. Systems are being brought online in a controlled, staged sequence to ensure a safe and stable recovery. Customer traffic remains rerouted away from the affected systems and will only be moved back once the location is fully verified as stable. Some management and reporting functions remain temporarily limited and are expected to recover progressively as systems come back online. We will provide the next update once the power-up sequence has progressed, at the latest by 15:00 UTC (17:00 CEST). If you are experiencing impact beyond what is described here, please contact our support team through the usual channels.
- monitoring · Aug 16, 2026, 10:10 AM UTC
Aug 16, 2026 - 10:10 UTC All services at the affected location (FFM7) are back up and operating as expected. We will continue to monitor the system health closely. Please note: customer BGP sessions towards FFM7 have not been re-enabled yet. They will be brought back gracefully after an additional monitoring period has passed, to ensure a stable and safe return of traffic. Customer traffic remains served via alternative locations until then and stays fully protected - no action is required on your side. We will provide the next update once customer BGP sessions are being re-enabled, at the latest by 14:00 UTC (16:00 CEST). If you are experiencing impact beyond what is described here, please contact our support team through the usual channels.
- resolved · Aug 16, 2026, 03:18 PM UTC
Aug 16, 2026 - 15:20 UTC All customer BGP sessions have been re-enabled and have re-established successfully. Infrastructure Protection services at FFM7 are fully active again, and transit connections have been restored. All services are operating normally. We will continue to monitor system health closely over the coming hours before resolving this incident. Please note: traffic statistics from the incident timeframe may currently not be displayed for some services. We are investigating whether this data can be restored and will handle this separately from the incident itself - live traffic data and reporting are working normally. Thank you for your patience during this incident. A root cause analysis will be made available to affected customers once our investigation is complete. If you are experiencing any residual issues, please contact our support team through the usual channels.
Latest: Aug 16, 2026 - 15:20 UTC All customer BGP sessions have been re-enabled and have re-established successfully. Infrastructure Protection services at FFM7 are fully active again, and…
-
See the full Link11 outage history
1 more incident in the last 90 days, plus the full multi-year archive of per-service events and update timelines.
Browse Link11 outage history →Or sign up free to get alerts when Link11 breaks · 10 free monitors · No credit card
Incident record
Since April 2026 · Statuspage by Atlassian · 8 components checked every 5 minutesThe longest incident in the last year, Reporting System Degradation on January 8, 2026, ran for 5 days. 15 maintenance windows announced in the same period.
Most affected components, last 12 months
- Infrastructure Protection11
- Link11 WAAP10
- Web DDoS Protection8
- Secure CDN5
- Bot Management4
Latest incidents
- Intermittent Connectivity issues at Ashburn site
We are currently experiencing intermittent connectivity issues at our Ashburn site. Link11 is actively working with its transport providers to restore services…
- Link11 Support Mailbox Outage
Dear valued Customer, We are currently experiencing an outage affecting the Link11 support mailboxes. During this time, emails sent to our support team may not…
- Intermittent phone lines issues
We are currently investigating some intermittent issues with our phone lines. Some of the calls are not being properly forwarded. Please use the following…
- Started Oct 30, 2026, 04:39 PM UTC · Resolved Oct 30, 2026, 10:04 PM UTC · 5h 24m
- Link11 Support Mailbox Outage ResolvedStarted Oct 30, 2026, 04:37 PM UTC · Resolved Oct 30, 2026, 06:54 PM UTC · 2h 16m
- Intermittent phone lines issues ResolvedStarted Oct 04, 2026, 07:51 PM UTC · Resolved Oct 05, 2026, 02:00 PM UTC · 18h 9m
- Started Sep 24, 2026, 08:55 PM UTC · Resolved Sep 24, 2026, 10:47 PM UTC · 1h 52m
- Connection issues in FFM7 (FR5) ResolvedStarted Aug 15, 2026, 05:09 AM UTC · Resolved Aug 16, 2026, 03:18 PM UTC · 1d 10h
- Started Aug 11, 2026, 04:07 PM UTC · Resolved Aug 11, 2026, 10:14 PM UTC · 6h 7m